展示を参照してください。 2 つのデータセンター ファブリックは VPC データセンター インターコネクトを使用します。SW1 のシステム MAC 値は次のとおりです。 00:23:04:ee:be:20。どの値 システムの MAC アドレスを設定する必要がありますか?
正解:B
In a vPC (Virtual Port Channel) data center interconnect, both vPC peer devices must have the same system MAC address to ensure that remote switches perceive them as a single logical switch. Since the system MAC value on SW1 is 00:23:04:ee:be:20, the same value must be configured on SW3 to maintain consistency in the vPC domain and ensure seamless communication between the two data center fabrics connected through this vPC interconnect. References: = The explanation can be inferred from Cisco's official documentation and resources related to configuring and managing vPCs, ensuring that both peer devices in a vPC domain are configured with identical parameters, including the system MAC address.